Aluminium cable

Supply formats:

  • ACSR

  • AACSR

  • AAC

  • ACSR/AW

  • AAAC

  • ACAR

  • ACSS

  • Earth

Definition: Aluminium conductors with steel core.Made up of several aluminium and galvanised steel wires bundled into concentric layers.

Data sheet: Aluminium cable

At Bronmetal we supply a variety of formats of high quality aluminium cable, also known as bare aluminium connectors.

Packaging. We supply aluminium cable in reels. The length will depend on the composition of the aluminium cable. See the section on aluminium cable packaging.

  • ACSR, ALUMINIUM CONDUCTORS STEEL REINFORCED aluminium cable
    DEFINITION: Aluminium conductors with steel core.
    Made up of several aluminium and galvanised steel wires bundled into concentric layers.
    MAIN APPLICATIONS: In medium, high and very high voltage overhead lines.
    STANDARDS: EN 50182, ASTM B-232, BS 215-2, DIN 48204, UNE 21018
  • AAC, ALL ALUMINIUM CONDUCTORS aluminium cable
    DEFINITION: Aluminium conductors. Made up of several aluminium wires bundled into concentric layers.
    Very high conductivity/weight ratio.
    MAIN APPLICATIONS: Conductor in high voltage substations, conductor in overhead distribution lines, conductor (compact) for insulated cables.
    STANDARDS EN 50182 , ASTM B-231 , BS 215-1 , DIN 48201-5 , UNE 21018
  • AAAC, ALL ALUMINIUM ALLOY CONDUCTORS aluminium cable
    DEFINITION: Aluminium alloy conductors. Made up of several aluminium wires bundled into concentric layers.
    MAIN APPLICATIONS: Low, medium, high and very high voltage overhead lines.
    STANDARDS: EN 50182 , ASTM B-399 , BS 3242 , DIN 48201-6 , UNE 21018
  • AACSR, ALUMINIUM CONDUCTOR STEEL REINFORCED aluminium cable
    DEFINITION: Aluminium alloy conductors with steel core. Made up of several aluminium alloy and galvanised steel wires bundled into concentric layers.
    MAIN APPLICATIONS: Low, medium, high and very high voltage overhead lines.
    STANDARDS: EN 50182, ASTM B711, UNE 21018
  • ACSR / AW, ALUMINIUM ALLOY CONDUCTOR ALUMINIUM CLAD STEEL REINFORCED aluminium cable
    DEFINITION: Aluminium alloy conductors with steel core. Made up of several aluminium and aluminium-clad steel wires bundled into concentric layers.
    MAIN APPLICATIONS: Medium, high and very high voltage overhead lines, especially in corrosive environments.
    Greater resistance to corrosion than ACSR and AACSR.
    STANDARDS: ASTM B-549, UNE 21 018
  • ACAR, ALUMINUM CONDUCTOR ALLOY REINFORCED cas. aluminium cable
    DEFINITION: Aluminium and aluminium alloy conductors. Made up of several aluminium and aluminium alloy wires bundled into concentric layers.
    STANDARDS: ASTM B524.
  • ACSS, ALUMINIUM CONDUCTOR STEEL SUPPORTED aluminium cable
    Aluminium conductors supported by steel bundled into concentric layers.
    STANDARDS: ASTM B856, ASTM B857, EN 50540.
  • OPGW, OPTICAL GROUND WIRE aluminium cable
    DEFINITION: Made up of an optical core of several fibres housed in an extruded aluminium tube into which one or more layers of aluminium-clad steel wires are bundled.
    STANDARDS: UNE-EN 61 232, IEC 60 794.
  • EARTH CABLE, ALUMINIUM-CLAD STEEL CONDUCTORS aluminium cable
    DEFINITION: Aluminium-clad steel wires.
    Made up of several aluminium clad steel wires bundled into concentric layers.
    MAIN APPLICATIONS: Earth cable in distribution lines, conductor in large crossings and rural electrification lines, fastening cable for guyed pylons.
    STANDARD: ASTM B-416

AAAC

ALL Aluminium ALLOY CONDUCTORS

Characteristics, according to the 50182:2001 Standard Type AL2 - Spain
Code Old code Cross section No. of wires Diameter Mass per unit of lenght Assigned tensile strenght Short-circuit resistance
Wire Conductor
mm2 mm mm kg / km kN Ω / km
28-AL2 D 28 27,8 7 2,25 6,75 76 9,05 1,193
43-AL2 D 40 43,1 7 2,8 8,4 117,7 14,01 0,7704
55-AL2 D 56 54,6 7 3,15 9,45 148,9 17,73 0,6087
76-AL2 D 80 75,5 19 2,25 11,3 207,4 24,55 0,442
117-AL2 D 110 117 19 2,8 14 321,2 38,02 0,2854
148-AL2 D 145 148,1 19 3,15 15,8 406,5 48,12 0,2255
188-AL2 D 180 188,1 19 3,55 17,8 516,3 59,24 0,1776
279-AL2 D 280 279,3 37 3,1 21,7 769,3 90,76 0,12
381-AL2 D 400 381 61 2,82 25,4 1 053,0 123,82 0,0882
454-AL2 D 450 454,5 61 3,08 27,7 1 256,1 147,71 0,074
547-AL2 D 550 547,3 61 3,38 30,4 1 512,7 177,88 0,0614
638-AL2 D 630 638,3 61 3,65 32,9 1 764,0 201,06 0,0527
NOTE - The external layer is wired in the “clockwise” direction (Z)

AAC

All Aluminium conductors

Characteristics, according to the 50182:2001 Standard Type AL1 - Spain
Code Old code Cross section No. of wires Diameter Mass per unit of lenght Assigned tensile strenght Short-circuit resistance
Wire Conductor
mm2 mm mm kg / km kN Ω / km
28-AL1 L 28 27,8 7 2,25 6,75 76,1 5,01 1,0268
43-AL1 L 40 43,1 7 2,8 8,4 117,8 7,33 0,663
55-AL1 L 56 54,6 7 3,15 9,45 149,1 9 0,5239
76-AL1 L 80 75,5 19 2,25 11,3 207,6 13,6 0,3804
117-AL1 L 110 117 19 2,8 14 321,5 19,89 0,2456
148-AL1 L 145 148,1 19 3,15 15,8 407 24,43 0,1941
188-AL1 L 180 188,1 19 3,55 17,8 516,9 30,09 0,1528
279-AL1 L 280 279,3 37 3,1 21,7 770,2 46,08 0,1033
381-AL1 L 400 381 61 2,82 25,4 1 054,1 64,77 0,0759
454-AL1 L 450 454,5 61 3,08 27,7 1 257,5 74,99 0,0637
547-AL1 L 550 547,3 61 3,38 30,4 1 514,4 90,31 0,0529
638-AL1 L 630 638,3 61 3,65 32,9 1 766 102,12 0,0453
NOTE - The external layer is wired in the “clockwise” direction (Z)

AACSR

Aluminium CONDUCTOR STEEL REINFORCED

Characteristics, according to the 50182:2001 Standard Tipo AL2/ST1A - España.
Code Old code Cross section No. of wires Wire diameter Diameter Mass per unit of lenght Assigned tensile strenght Short-circuit resistance
Al Steel Total Al Steel Core Conductor
mm2 mm2 mm2 Al Steel mm mm mm mm kg / km kN Ω / km
27-AL2/4-ST1A DA 30 26,7 4,45 31,1 6 1 2,38 2,38 2,38 7,14 107,7 13,75 1,2474
47-AL2/8-ST1A DA 56 46,8 7,79 54,6 6 1 3,15 3,15 3,15 9,45 188,6 23,77 0,7121
67-AL2/11-ST1A DA 78 67,3 11,2 78,6 6 1 3,78 3,78 3,78 11,3 271,6 33,55 0,4945
94-AL2/22-ST1A DA 110 94,2 22 116,2 30 7 2 2 6 14 432,2 56,36 0,3563
119-AL2/28-ST1A DA 145 119,3 27,8 147,1 30 7 2,25 2,25 6,75 15,8 547 71,33 0,2815
147-AL2/34-ST1A DA 180 147,3 34,4 181,6 30 7 2,5 2,5 7,5 17,5 675,3 87,03 0,228
226-AL2/53-ST1A DA 280 226,4 52,8 279,3 30 7 3,1 3,1 9,3 21,7 1 038,4 131,71 0,1483
NOTE - The external layer is wired in the “clockwise” direction (Z)

ACAR

Aluminum Conductor Alloy Reinforced

Aluminium and aluminium alloy conductors. Composed of different aluminium and aluminium alloy wires, wired in concentric layers STANDARDS: ASTM B524.

ACSR

Steel-reinforced aluminium conductors

Characteristics, according to the 50182:2001 Standard Type AL1/ST1A - Spain.
Code Old code Cross section No. of wires Wire diameter Diameter Mass per unit of lenght Assigned tensile strenght Short-circuit resistance
Al Steel Total Al Steel Core Conductor
mm2 mm2 mm2 Al Acero mm mm mm mm kg / km kN Ω / km
27-AL1/4-ST1A LA 30 26,7 4,45 31,1 6 1 2,38 2,38 2,38 7,14 107,8 9,74 1,0736
47-AL1/8-ST1A LA 56 46,8 7,79 54,6 6 1 3,15 3,15 3,15 9,45 188,8 16,29 0,6129
67-AL1/11-ST1A LA 78 67,3 11,2 78,6 6 1 3,78 3,78 3,78 11,3 271,8 23,12 0,4256
94-AL1/22-ST1A LA 110 94,2 22 116,2 30 7 2 2 6 14 432,5 43,17 0,3067
119-AL1/28-ST1A LA 145 119,3 27,8 147,1 30 7 2,25 2,25 6,75 15,8 547,4 54,03 0,2423
147-AL1/34-ST1A LA 180 147,3 34,4 181,6 30 7 2,5 2,5 7,5 17,5 675,8 64,94 0,1963
242-AL1/39-ST1A LA 280 HAWK 241,6 39,5 281,1 26 7 3,44 2,68 8,04 21,8 976,2 84,89 0,1195
337-AL1/44-ST1A LA 380 GULL 337,3 43,7 381 54 7 2,82 2,82 8,46 25,4 1 274,6 107,18 0,0857
402-AL1/52-ST1A LA 455 CONDOR 402,3 52,2 454,5 54 7 3,08 3,08 9,24 27,7 1 520,5 123,75 0,0719
485-AL1/63-ST1A LA 545 CARDINAL 484,5 62,8 547,3 54 7 3,38 3,38 10,1 30,4 1 831,1 149,04 0,0597
565-AL1/72-ST1A LA 635 FINCH 565 71,6 636,6 54 19 3,65 2,19 11 32,9 2 123,0 174,14 0,0512
NOTE - The external layer is wired in the “clockwise” direction (Z)

ACSR / AW

Aluminium ALLOY CONDUCTOR ALUMINIUM CLAD STEEL REINFORCED

Characteristics, according to the UNE 21-018-80 Standard
Designation Cross section Equivalence in copper Diameter Composition Tensile strenght kgf _______ daN Electrical resistance at 20º Ω/km Mass Kg / Km Elasticity modulus kgf / mm2 _________ N / mm2 Linear expansion coefficient ºC X 10-6
Al ARL Total mm Aluminium wires ARL wires
mm2 mm2 mm2 mm2 Core Total Ø Ø Al ARL Total kg / km kN
LARL- 30 26,7 4,4 31,1 17,5 2,38 7,14 6 2,38 1 2,38 1 040 1,0175 73,2 29,3 102,5 7 600 19,3
1 020 75 000
LARL-56 46,8 7,8 54,6 30 3,15 9,45 6 3,15 1 3,15 1 750 0,5808 128,3 51,4 179,7 7 600 19,3
1 720 75 000
LARL-78 67,4 11,2 78,6 44 3,78 11,34 6 3,78 1 3,78 2 350 0,4033 185 74 259 7 600 19,3
2 300 75 000
LARL-145 119,3 27,8 147,1 78 6,75 15,75 30 2,25 7 2,25 5 620 0,2244 330 184 514 7 600 18
5 510 75 000
LARL-180 147,3 34,3 181,6 97 7,5 17,5 30 2,5 7 2,5 6 760 0,1818 407 227 634 7 600 18
6 630 75 000
LARL-280 Hawk 241,7 39,4 281,1 157 8,04 21,8 26 3,44 7 2,68 8 940 0,1131 667 262 929 7 300 19,1
8 760 72 000
LARL-380 Gull 337,3 43,7 381 217 8,46 25,38 54 2,82 7 2,82 11 180 0,082 932 290 1 222 6 700 19,5
10 960 66 000
LARL-455 Condor 402,3 52,2 454,5 259 9,24 27,72 54 3,08 7 3,08 13 200 0,0688 1 112 345 1 457 6 700 19,5
12 940 66 000
LARL-545 Cardinal 484,5 62,8 547,3 312 10,14 30,42 54 3,38 7 3,38 15 630 0,0571 1 339 416 1 755 6 700 19,5
15 320 66 000
LARL-635 Finch 565 71,6 636,6 364 10,95 32,85 54 3,65 19 2,19 18 100 0,049 1 562 475 2 037 6 500 19,6
17 750 64 000
The characteristics of these conductors are specified in the following standards: UNE 21 014 (I) Aluminium wires for overhead power line conductors. UNE 21 041 Aluminium-clad steel wire for cable cores, used in overhead power lines UNE 21 058 Aluminium-clad steel and aluminium wires, used in overhead power lines.  

ACSS

ALUMINIUM CONDUCTOR STEEL SUPPORTED

Aluminium conductors with steel support, wired in concentric layers. STANDARDS: ASTM B856, ASTM B857, EN 50540.

BOBINES

Width Height
(mm) (mm)
DIN 1080 1 080 640
DIN 1270 1 270 700
DIN 1320 1 320 740
DIN 1400 1 400 930
DIN 1600 1 600 820
DIN 1800 1 800 820
1 800 1 130
1 800 1 150
DIN 1950 1 950 1 130
DIN 2290 2 290 1 346
DIN 2425 2 425 1 560
DIN 2600 2 600 1 560
* The length will depend on the composition of the aluminium cable.

GROUNDING CABLE

ALUMINIUM-CLAD STEEl CONDUCTORS

Characteristics, according to the ATSM B-416 Standard
No. and size of the wires Surface area Diameter Diameter Tensile strengh Maximum resistance at 20º Standard weight
mm2 mm Ø  (mm) Ω / Km Kg / Km
3 No. 5AWG 50,29 9,96 3 4,62 5,447 16997 334,1
3 No. 6AWG 39,8 8,86 3 4,11 4,575 21476 264,4
3 No. 7AWG 31,74 7,91 3 3,67 3,859 26935 210,8
3 No. 8AWG 25,04 7,03 3 3,26 3,188 34136 166,3
3 No. 9AWG 19,95 6,27 3 2,91 2,54 42841 132,5
3 No. 10AWG 15,81 5,58 3 2,59 2,012 54081 105
7 No. 5AWG 117,35 13,86 7 4,62 12,04 0,7299 781,1
7 No. 6AWG 92,87 12,33 7 4,11 10,113 0,9222 618,1
7 No. 7AWG 74,05 11,01 7 3,67 8,53 11566 492,9
7 No. 8AWG 58,43 9,78 7 3,26 7,046 14659 388,9
7 No. 9AWG 46,56 8,73 7 2,91 5,615 18397 309,9
7 No. 10AWG 36,88 7,77 7 2,59 4,448 23224 245,5
7 No. 11AWG 29,08 6,9 7 2,3 3,507 29449 193,6
7 No. 12AWG 23,1 6,15 7 2,05 2,786 37070 153,8
19 No. 5AWG 318,51 23,1 19 4,62 32,68 0,27 2128
19 No. 6AWG 252,07 20,55 19 4,11 27,451 0,3411 1684
19 No. 7AWG 200,99 18,35 19 3,67 23,154 0,4278 1343
19 No. 8AWG 158,59 16,3 19 3,26 19,126 0,5422 1060
19 No. 9AWG 126,37 14,55 19 2,91 15,24 0,6805 844
19 No. 10AWG 100,1 12,95 19 2,59 12,072 0,859 669

OPGW

Optical Ground Wire

Composed of an optical core with different fibres, hosted inside an extruded aluminium tube, in which one or more layers of aluminium-clad steel wire layers are wired. STANDARDS: UNE-EN 61 232, IEC 60 794.

Documentation download

Title
Other languages
Type
Created
Type Catalogue
Created 03/04/2023
Type Technical sheets
Created 07/01/2020
You may also like

Aluminium tubes

Flexicopper: Flexible copper flat bars

Bare copper cable